Modbus/TCP 7-7
© 2011 Pyramid Solutions Inc. Publication PUB-AB7603-014
The Command register is a bit string with the following bit definitions.
Bit Description
0 Local Run Mode. Used in conjunction with the Sys-
tem Run Mode bit in the Run/Idle register to deter-
mine the run mode of the BridgeWay. Both bits must
be set for the BridgeWay to be in Run mode; other-
wise the module will be in Idle mode.
1 Fault. Sets a fault condition in the BridgeWay.
2 Disable DeviceNet network.
3 Not used.
4 Reset the BridgeWay module.
5-31 Not used.
Table 7-10 Command Register Bit Definitions